Superheat and subcooling are 2 temperature differences measured at opposite ends of the circuit, and they are read together. Their 4 combinations point at 4 different faults, and only 2 of the 4 are corrected by adding or removing refrigerant. The other 2 are a metering device or a restriction.
A pressure gauge tells you what a pressure is. It does not tell you why.
Superheat and subcooling turn two pressures and two temperatures into a statement about what the refrigerant is doing. Superheat says what is happening on the low side, where the refrigerant finished boiling. Subcooling says what is happening on the high side, where it finished condensing.
Taken alone, each number has several explanations. Taken together, the pair narrows a no-cool call to one of four causes before a part is ordered.
The target numbers are not universal. They come from the manufacturer for that model, under the conditions you are measuring in, which is why a charging chart beats a remembered figure every time.
Superheat is how much warmer the refrigerant vapor is than the temperature at which it boiled, at the pressure it is under. It exists only after the refrigerant has fully turned to vapor.
Taking it is three steps and one lookup.
Where you stand changes what the number means. At the evaporator outlet it describes the evaporator. At the compressor inlet it describes the evaporator plus everything the suction line picked up on the way, which on a long run through a hot kitchen can be a large part of the reading.
Low superheat means liquid refrigerant is reaching further down the coil than it should, and the extreme case is liquid arriving at the compressor. High superheat means the refrigerant ran out of liquid early and the last part of the coil is doing nothing useful.
Subcooling is how much colder the liquid refrigerant is than the temperature at which it condensed, at the pressure it is under. It is measured on the liquid line, usually at the condenser outlet or close to the metering device.
Same arithmetic in the other direction. Convert the liquid line pressure to its saturation temperature, measure the actual liquid line temperature, and subtract the measurement from the saturation temperature.
Subcooling answers a different question than superheat. It tells you whether there is a solid column of liquid arriving at the metering device. Without that, the device cannot meter anything, because it was designed to control liquid and not a mixture of liquid and vapor.
Which is why low subcooling and high superheat so often appear together. One is the cause and the other is the consequence.
They come from the equipment, not from memory. The manufacturer sets the target for that model at the conditions it is running in, and it is printed on the data plate, in the service literature or on the chart inside the panel.
Published guidance varies, and that variation is the point rather than a problem with the sources. A reach-in at 70F ambient and a remote condensing unit on a roof at 95F have different correct answers, and the same equipment has a different target in July than in January.
Two rules survive every disagreement about the exact figure.
Record the ambient temperature next to every reading. A superheat figure without the conditions it was taken under cannot be compared to the one from the last visit, which turns two useful measurements into two numbers in a notebook.
This is the table worth carrying. Read the pair, not either number alone.
| Superheat | Subcooling | What it points at | What to do next |
|---|---|---|---|
| High | Low | Undercharge, which in a sealed system means a leak | Find the leak and repair it before adding anything |
| Low | High | Overcharge, or a condenser that cannot reject its heat | Check the condenser and the fan first, then recover refrigerant if the charge really is high |
| High | High | A restriction between condenser and evaporator, or a metering device closed too far | Look at the filter drier, the liquid line and the valve. Refrigerant will not fix this |
| Low | Low | The metering device is passing too much, or the load on the coil is far above design | Check the valve and its sensing bulb, and check what the kitchen just loaded into the box |
The third row is the one that costs money. High and high looks like a charge problem to anyone reading one number, and a technician who adds refrigerant watches the subcooling climb while the superheat sits where it was. That behavior is itself the diagnosis, and it is worth recognizing before the cylinder comes off the van.
The fourth row is the one that is often not a fault at all. A cooler that just took 200 pounds of warm product has a load far above design and will read low on both until it catches up.
Four of them account for most wasted trips, and none of them is about the arithmetic.
A fifth one deserves its own sentence. Taking readings on a coil choked with frost or a condenser packed with grease measures the blockage, not the charge, and the readings come good the moment the equipment is clean.
Because both of them move superheat and subcooling without anything being wrong with the refrigerant, and connecting gauges is not free. Every connection is an opportunity to lose charge and introduce air or moisture.
The sequence that saves the most time on a no-cool call in a commercial kitchen:
On the kind of equipment a kitchen runs, the first four steps resolve a large share of calls. The equipment cares about the air it is given more than it cares about anything a technician does with a manifold. The wider mechanics of that are in how commercial refrigeration systems work.
A superheat reading is only a diagnosis on the day. It becomes a trend when the same number from the same point exists from 6 months ago, and a trend is what justifies replacing a unit instead of repairing it again.
Those belong on the equipment record rather than in a job note. A reading attached to a job is attached to a day. The same reading attached to the unit builds a history that the next technician reads before getting out of the van, and the compliance side of the same records is covered in EPA 608 and refrigerant handling.
Roopairs runs a product tour where you can see equipment records per asset, service history and technician documentation in one place.
“My favourite thing about Roopairs is the equipment tracking. Being able to have the history at the spur of the moment when the customer requests it. The old school version would be me flipping through my day minder going, when were you there last and worked on the bar cooler. With Roopairs I can just pull open the equipment, type in the serial number, and the repair history is there. Flawless.” — ProTemp Solutions
Read the suction pressure, convert it to the saturation temperature for the refrigerant in the system, measure the actual line temperature at the same point, and subtract the saturation temperature from the measured temperature. The result describes the evaporator at the coil outlet and the evaporator plus the suction line at the compressor.
Read the liquid line pressure, convert it to its saturation temperature, measure the actual liquid line temperature, and subtract the measurement from the saturation temperature. It is taken on the liquid line, and it tells you whether solid liquid is arriving at the metering device.
It points at an undercharge, and in a sealed system an undercharge means refrigerant left through a leak. The leak gets found and repaired before anything is added, because topping up a leaking system returns the same call in a few weeks with the same reading.
A restriction between the condenser and the evaporator, or a metering device that is closed too far. Liquid is stacking up on the high side and not enough is reaching the coil. Adding refrigerant does not correct it, and the usual places to look are the filter drier, the liquid line and the valve.
Whatever the manufacturer specifies for that model at the conditions you are measuring in, taken from the data plate, the service literature or the charging chart. Published general ranges vary because the correct figure depends on the equipment, the ambient and the load, so a chart beats a remembered number.
Yes. A thermostatic expansion valve actively controls superheat, so on that kind of system the figure is what the valve is holding rather than a direct reflection of the charge. A superheat that does not move while subcooling climbs during charging is the signature of a valve problem rather than a charge problem.
Because the circuit is not at steady state. For a period after defrost, after a door has been held open or after warm product has been loaded, pressures and temperatures are still moving and any reading is a snapshot of a transient. Let the unit settle into a normal running cycle first.